Transformer Turns Ratio Meter
Introduction
YT-A transformer turns ration meter is suitable for the turns ratio measurement of power transformers upto 1000kV, current transformers, voltage transformers and Z type transformers. It has L-N voltage measurement, great convenience for wiring connection, fast test speed and high accuracy.
Features
- Touch panel, easy for operation;
- Current measurement function, much more sensitive to detect the short circuit in the turns;
- Fast test speed, one time wiring can fulfill 3 phase turns ratio measurement within 10 s;
- 50 test data storage;
- LCD, thermal printer, RS485 communication port and USB port;
- With transformer short circuit protection, turns short circuit protection, wrong connection of HV and LV terminals protection;
Technical Parameters
Displayed digits | 5 digits | ||
Output voltage | 160V, AC | 10V,AC | Automatic(inbuilt DC) |
Range | 0.9-10000 | 0.9-500 | 0.9-5000 |
Accuracy | ±0.1% when ratio <2000 | ±0.1% when ratio <150 | ±0.1% when ratio <1000 |
±0.3% when ratio 2000~10000 | ±0.3% when ratio 150~500 | ±0.3% when ratio 1000~5000 | |
Resolution | 0.0001 | ||
Power supply | AC220V±10%, 50/60Hz±1Hz | Lithium battery (optinal) | |
Temperature | -20~40ºC | ||
Relative humidity | ≤80% RH, no condensing | ||
Dimension | 360mm(L)*280mm(W)*160mm (H) | ||
Net weight | 6kgs |